Two-Wire Dry-Contact Generator Autostart Wiring Guide: Automating Off-Grid Battery Charging

Trudging through 2 feet of snow at 2:00 AM with a flashlight to pull-start a portable generator when your battery hits 10% is miserable. Learn how to wire the NO/NC Dry-Contact Relay inside your hybrid inverter to start and stop your propane/diesel generator automatically.

Recommended PV Array
Any Off-Grid or Hybrid PV Array
48V LFP Battery Capacity
14.3 kWh – 60 kWh 48V LFP Bank
Inverter & Bus Topology
EG4 18kPV / 6000XP, Sol-Ark 15K, or Victron Cerbo GX Dry-Contact Relay
AWG Wire Gauge & Protection Spec
18/2 Shielded Thermostat/Control Wire (Dry Contact) + 6 AWG / 8 AWG AC Generator Feed
Design Autonomy Target
365-Day Hands-Free Winter Backup Automation

📐 Step-by-Step Off-Grid Engineering & Sizing Rules

01

How a Dry-Contact (NO / COM / NC) Relay Works: Every serious off-grid inverter (EG4 18kPV, 6000XP, Sol-Ark 15K, Victron MultiPlus/Cerbo) has a small 2-pin "GEN DRY CONTACT" terminal block. It does NOT output voltage—it simply acts like a robot finger that closes a switch when Battery SoC drops to 15% and opens the switch when Battery SoC reaches 80%.

02

True 2-Wire Start Generators vs 3-Wire / Push-Button Generators: Cummins Onan, Kohler (with 2-wire kit), Generac (via Atkinson GSCM-Mini controller), Westinghouse iGen11000DFc (with auto-choke module), and EcoFlow Dual-Fuel Smart Generator support automated start/stop.

03

Programming Quiet Hours Lockout: Configure your inverter Gen Exercise & Quiet Hours window (e.g., Lockout 10:00 PM to 7:00 AM) and set an Evening Pre-Charge check at 7:00 PM: if battery SoC is below 35% at 7:00 PM, the generator runs from 7:00 PM to 9:00 PM so it never wakes you up at 3:00 AM!

04

Warm-Up & Cool-Down Timers: Set a 60-second Warm-Up delay before the inverter applies charging load so cold engine oil circulates first, and a 120-second Cool-Down delay before engine shutoff.

⚡ Conductor Sizing, Fusing & Conduit Schedule

Open Full Single-Line Wiring Schematics →
  • Control Signal: Inverter Dry-Contact [NO] and [COM] terminals -> 18/2 Jacketed Control Cable in separate conduit from AC power -> Generator 2-Wire Start Terminal Block (or GSCM-Mini Auto-Choke Module).
  • Battery Trickle Maintainer: Run a dedicated 120V outlet or small 20W solar trickle panel to the generator's 12V starter battery so the starter battery never dies in January!

📦 Recommended Direct-to-Homesteader Hardware Kits

Skip the 100% turnkey installer markup. Order UL-certified 48V LFP racks, hybrid inverters, and bifacial solar palettes direct from verified wholesale distributors:

Frequently Asked Questions: 2-Wire Generator Autostart Wiring

Can I add 2-wire autostart to a regular electric-start portable generator?

Only if the generator has an automatic choke (or fuel injection EFI) and you install a $220 Atkinson Electronics GSCM-Mini generator start controller module, which converts your inverter's simple 2-wire dry contact closure into timed choke, crank, oil-pressure sense, and kill sequences.