Sol-ArkFault F13 / F18 / F20 (Hardware Overcurrent)High — Inverter Relay Reset or Arc/Surge Trip

Sol-Ark 15K / 12K Fault F13, F18 & F20 (Grid Mode Changed / Overcurrent / DC Bus): Complete Fix

Exact Field Symptom:

Sol-Ark 15K touch screen logs Fault F13 (Grid Mode Changed), F18 (AC Overcurrent Hardware), or F20 (DC Overcurrent Hardware) and clicks its internal transfer relays.

DIY Safety Classification:

Safe Parameter & CT Check

🔬 Root Cause Electrical Physics

F13 is an informational reset when grid parameters or CT settings are changed. F18 and F20 occur when instantaneous AC or DC current exceeds the 275A/300A IGBT hardware protection threshold—most often triggered by (1) an un-soft-started 5-ton AC compressor, (2) a shorted appliance on the Load breaker, or (3) reversed/loose CT sensor leads causing the inverter control loop to oscillate.

⚡ Step-by-Step Multimeter & Diagnostic Test Procedure

TEST 1

Navigate to the Sol-Ark touch screen -> Home Icon -> Gear Icon -> Battery Setup and verify "Max A Charge" and "Max A Discharge" match your battery bank BMS limits (275A max on Sol-Ark 15K).

TEST 2

Check the Dial/Status screen for L1 and L2 CT watt readings: if one leg shows a negative (-) sign during normal grid import, your CT clamp arrow is pointing the wrong way!

🛠️ Safe DIY Reset & Remediation Steps

  1. 1.Verify both L1 and L2 CT clamps are snapped completely shut around the utility service entrance conductors with the arrow pointing TOWARD THE INVERTER / HOME LOADS (away from the utility meter).
  2. 2.Never extend Sol-Ark CT wires with unshielded thermostat wire—use only twisted-pair shielded Cat6 cable.
  3. 3.Perform a full cold boot: Turn off AC Grid breaker, turn off Load breaker, turn off PV switch, turn off Battery breaker, wait 5 minutes until the LCD screen goes completely black, then power up Battery -> PV -> Grid -> Load.

👷 When to Escalate to a Licensed Solar Electrician

If F18 or F20 recurs immediately upon turning on the Battery breaker with all AC loads disconnected, an internal IGBT bridge module has shorted and requires Sol-Ark 10-year warranty RMA.

🔋 Direct Replacement & Upgrade Hardware

Compare Sol-Ark 15K against the EG4 18kPV (/go/eg4) in our head-to-head engineering battle.

Frequently Asked Questions: Sol-Ark 15K Fault F13 / F18 / F20 Fix

Is Sol-Ark Fault F13 an actual hardware breakdown?

No! Fault F13 ("Grid Mode Changed") simply means the inverter re-initialized its grid synchronization profile after a firmware update, a voltage/frequency parameter change, or a grid brownout recovery.

Other Critical Inverter & Battery Diagnostics