NEC Section 705.11 (Supply-Side Source Connections — 2020/2023 Code Revisions)

NEC 705.11 Supply-Side Tap (Line-Side Connection) Engineering & Wire Sizing

Everything electricians and DIY permit applicants need to know about NEC 705.11 Supply-Side Taps: minimum 6 AWG copper wire mandate, 10-foot tap conductor length limit, UL-listed IPC connectors, and fused AC disconnects.

Service & Panel Scope
100A–400A Residential & Light Commercial Services
Cost & Permit Impact
Allows 60A–100A+ solar/battery interconnection on a full 200A panel

1. NEC Code Rules & Electrical Engineering Breakdown

RULE 1

NEC 705.11(B) Minimum Conductor Size (Never Smaller Than 6 AWG Cu!): Even if you are only connecting a small 20A solar inverter via a Supply-Side Tap, NEC 705.11(B) strictly prohibits using tap conductors smaller than 6 AWG copper or 4 AWG aluminum on the supply side of the service disconnect because fault current ahead of the main breaker is limited only by the utility street transformer!

RULE 2

NEC 705.11(C) Maximum 10-Foot Tap Length to Fused Service Disconnect: For single-family dwellings, the supply-side tap conductors from the point of connection on the service entrance wires to the new Solar Fused Service Entrance Disconnect must not exceed 10 feet (3.0m) inside a raceway.

RULE 3

UL-Listed Connectors Required (NEC 705.11(E)): Splices or taps on service entrance conductors must use connectors explicitly listed for "Service Entrance / Supply-Side Tap" use (such as Ilsco KUP-L-Tap IPCs or NSi Polaris Grey/Black multi-tap blocks)—never standard split-bolts without listing.

2. Field Calculation Worksheet & Amperage Table

NEC 705.11 SUPPLY-SIDE TAP HARDWARE CHECKLIST
------------------------------------------------------------------
1. Tap Connectors:  UL-Listed Insulation Piercing Connectors (Ilsco IPC) or Polaris
2. Tap Conductors:  Min 6 AWG Cu THHN/THWN-2 (Up to 60A) or 3 AWG Cu (100A)
3. Tap Length:      ≤ 10 Feet in EMT / Rigid / Schedule 80 PVC Conduit
4. Disconnect:      60A or 100A Service-Entrance Rated Fused AC Switch (with Class R/J Fuses)
5. Grounding:       Neutral bonded to Enclosure inside the Fused Service Switch (NEC 250.24)

3. Recommended UL-Listed Hybrid Hardware

Run Interactive NEC 220 Critical Loads Sizer →
EG4 18kPV Hybrid Inverter (Direct Line-Side or Pass-Through Ready)
Interconnects cleanly via 60A–200A Fused Service Disconnect
Check Wholesale Price →
EcoFlow Whole-Home Backup Hub
Seamless Subpanel or Service Tap Integration
Check Wholesale Price →

Inspector & NEC Compliance FAQ

Why must the AC disconnect on a Supply-Side Tap be FUSED and Service-Entrance (SE) rated?

Because a Supply-Side Tap connects ahead of your main breaker, there is zero overcurrent protection between the utility transformer and your tap wires! The new disconnect IS a Service Entrance Disconnect and must contain current-limiting fuses (not an unfused pull-out) and a neutral-to-ground bond.

Does adding a Supply-Side Tap violate the "Six Disconnect Rule" in NEC 230.71?

Under the 2020 and 2023 NEC 230.71, new services cannot rely on 6 switches in a single enclosure, but NEC 230.82(6) and 705.11 explicitly permit an external supply-side solar/storage disconnect mounted in a separate enclosure adjacent to the main service.

More NEC 220 & 705 Electrical Engineering Guides